Thank you for your interest in TEB122050WL available NSN part on NSN Sphere. Circuit Breaker is listed with the part number TEB122050WL, and its manufacturer is General Electric Inc. This NSN part is currently available for purchase through our website today, and you may begin the process by filling out the following RFQ form. By providing us with information such as what parts you need, when you need them by, and your target price, our team can present you with a personalized quote that has been specifically tailored to fit your individual needs and requirements. Once you have submitted your request, a dedicated account manager will review and reach out to you in 15 minutes or less to continue the purchasing process.
As a leading online distributor of NSN parts like TEB122050WL, we provide customers access to an expansive database of new, used, and obsolete items that have been sourced from top global manufacturers such as General Electric Inc. If you are facing an AOG situation or time constraint, we provide same-day delivery and expedited shipping on a number of items. Get started on the purchasing process for NSN 5925010265114 under FSC 5925 Circuit Breakers and experience how NSN Sphere can serve as your strategic sourcing partner for all of your operational needs.
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.3125 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.1875 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.87501 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.90625 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 80.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 325.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 130.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 13.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 70.000 MAXIMUM AT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FEAT | SPECIAL FEATURES | WITH LINE AND LOAD LUGS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
SUPP | SUPPLEMENTARY FEATURES | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 DC IN ADDITION TO CPRF |
![]() |